2113 SDS2 Trip Computer CPU Power Supply 电源

Tyne’s replacement power supply for the SDS2 Trip Computer CPU was designed to satisfy the demanding Nuclear Technical Specification of the original power supply that has been in service for 30 years. The new model has a completely redesigned circuit board using high quality, modern electronic components.

Tyne的更换电源为 SDS2 跳闸计算机 CPU 的设计, 以满足苛刻的核技术规格的原始电源已在服役了30年。新的模型有一个完全重新设计的电路板使用高品质, 现代电子元件。

Nuclear power plant owners have expressed recent concerns regarding the quality of replacement power supplies from some vendors because of use of commercial components of sub-standard quality. To address this issue, Tyne designed its power supply from scratch, using custom-wound transformers, and all components positioned for easy inspection by Tyne and its customers.核电厂业主最近对一些供应商更换电源的质量表示关注, 因为使用了分标准质量的商业部件。为解决这一问题, Tyne从零开始设计其电源, 使用自定义缠绕变压器, 以及所有组件的位置, 以方便地检查, 由 Tyne和其客户。

Specifications

Input 115 VAC
Outputs
  • +5 Vdc output at 20 amps.- Ripple & noise = 25mV(p-p)
  • +12 Vdc output at 12 amps – Ripple & noise = 25mV(p-p)
  • +15 Vdc output at 0.50 amps – Ripple & noise = 0.8 mV(p-p)
  • –15 Vdc output at 0.50 amps -Ripple & noise = 0.8 mV(p-p)
  • Each side of the centre tapped 31.6-volt AC output transformer (15.8 volts to centre tap of transformer)
Efficiency 80% overall
Stability Semi-regulated output for bus stability
MTBF 40 years
Qualification Testing
  • Seismic
  • Aged for equivalent of 30 years
  • Thermal performance 10ºC to 50ºC , ambient condition -18°C to +60°C
  • Relative humidity 95% RH
  • MIL STD 461E for Electromagnetic Interference Emissions and Susceptibility Conducted Susceptibility, 30 Hz to 150 KHz, Power Lead. Method CS101
  • Conducted Susceptibility, bulk cable injection, 10 kHz to 200 MHz CS114
  • Conducted Susceptibility, bulk cable injection, Impulse excitation: CS115
  • Conducted Susceptibility, damped sinusoidal transients, cables and power leads 10 kHz to 100 MHz. CS 116
  • Radiated Susceptibility, Magnetic Fields 30 Hz to 100 kHz RS101
  • Radiated Susceptibility, electric field, 2 MHz to 500 MHz RS103
  • Conducted Emission Power Leads CE102: 10 KHz to 10 MHz.
  • Radiated Emissions, RE 102 Electric Field 10 kHz to 18 GHz (test to 500 MHz only).
Parallel operation supported
Cooling No fan required for cooling
Circuit Protection Over–current, over–voltage, reverse voltage and over–temp protection
Line regulation < 0.4% over the variation range
Load Regulation < 0.4% from no load to full load
Over voltage protection 125% of the output DC voltages
ResponseTime 1μs to 1% after a 25% load change at 5A/μs
Hold-up time 20 msec
Fold back current limit with automatic recovery after overload is removed.
Quality Assurance NQA-1, CSA-Z299.1, CSA-N286.2