MR5-200C 微欧姆计

The MICRO-OHMMETER MR5-200C is used to determine electric resistances on very low – resistance objects (e. g. bus bars, any connectors) while using a very high, continous flowing measurement current. The MR5-200C is able to generate a stable maximum current up to 200 A.

微欧姆计MR5-200C用于测量极低电阻物体(例如母线、任何连接器)上的电阻,同时使用非常高的连续流动测量电流。MR5-200C能够产生稳定的最大电流,最高可达200 A。

TEST CURRENT max. 200A (True DC). Increment 1 A.
Adjustable and presetable from 0 to 100%
0-199.9 µΩ (test current: up to 200 A).

0-1.999 mΩ (test current: up to 200 A).

0-19.99 mΩ (test current: up to 100 A).

0-199.9 mΩ (test current: up to 20 A).

0-1999 mΩ (test current: up to 2 A).

READING RESOLUTION 0.1 μΩ for R < 200 μΩ.

1 μΩ for R < 2000 μΩ.

10 μΩ for R < 20 mΩ.

OUTPUT VOLTAGE 4..5 Vdc @ all currents.
DISPLAY 4 digits result, current and time
LCD 9mm character height with backlight
TOTAL RESISTANCE max. 20 mΩ @ 200A.

max. 40 mΩ @ 100A.

MEASUREMENT PRINCIPLE Four-terminal due to Kelvin
Protects the instrument from overheating.
CONTINUOUS OPERATION TIME At 200 A this device should not be used continously for more than 30 minutes (overheat protected). At 100 A the measuring time is unlimited.
BASIS ACCURACY ± 0.3 % of reading ± 0.1 % of Range.
CURRENT FLOW DURATION The duration (time) for steady current flow can be easily set to 1,2,5,10,20s. ….up to 600s or unlimited (o.h. protected).
ADVANCED FEATURES Digital direct reading of resistance, current, measuring time and updated every second
BUILT-IN MEMORY Storage of 1000 test readings.
INTERFACE RS232 @ 2400, 4800, 9600 baud. , USB-B
ENVIRONMENTAL
PROTECTIONS
IP54 (with closed lid).
SAFETY CLASS Meets the requirements of IEC 61010-1:1990, IEC 61010-1:1992 amendment 2.
POWER SUPPLY 90~264 VAC – 47~63Hz / 127~370VDC
OPERATING TEMPERATURE -5°C to 50°C.
STORAGE TEMPERATURE -40°C to 85°C.
HUMIDITY RANGE 10~95 % of RH (non condensing).
EQUIPMENT WEIGHT Approx. 9.5 kg. (without cables)
DIMENSIONS 410W x 330D x 180H mm.
PRINTER Thermal printer