The precision holding device PWD2000/P is used for the determination of the electric resistance per meter of power and medium voltage cables. The measurement is based on the 4-pole method according to Kelvin in order to eliminate the feed line resistances. The measuring current is supplied via hydraulic operated jaws, the measuring voltage picked up via spring-supported taps, with a distance between the taps of 1000 mm (+/- 0,1mm).
精密保持装置PWD 2000/P用于测量每米电力和中压电缆的电阻。为了消除馈线电阻,根据开尔文的四极法进行了测量。测量电流通过液压操作的嘴提供,测量电压通过弹簧支撑的水龙头获得,水龙头之间的距离为1000 mm(/-0,1mm)。
Measuring distance | 1000 mm ± 0,1 mm |
Length of test object | 1500 .. 2000 mm (depends on sq.mm) |
Cross Section (Model 2000): | 16 mm² – 800 / 1200 / 2500 sq.mm |
Measuring current | 20 A max. (Micro Ohmmeter) |
Water flow version | |
Temperature probe | PT100 1/10 DIN (high precision) |
Bath | Water capacity approx. 15 l |
Circulation | integrated water flow system |
Circulation pump | 230 V AC or 115 V AC |
Air Reposing | |
Trough | protected against air flow from outside |
Temperature Probe | Infrared with automatic adjust control for high precision |
Hydraulic Contacts | |
Nominal pressure | up to 80,000 N |
Holding / release of test object | by switch (open / close) |
Security | Holding procedure only by closing covers |
Longitudinal feed force (model L) | Option |
Model overview: | |
PWD 2000 AL-Co W/A | no longitudinal tension device provided |
PWD 2000 AL-Co W/A-L | Tensile force required can be adjusted. |