Bieler+Lang GmbH Gas Detection System type : GMC Ecoline 8304 12.600742.2 气体检测系统
Approved to EN 50194
The system is designed to reliably detect natural gas an LPG. Up to four hazard zones can
be monitored. When an alarm situation arises, the controller switches the technical safety
measures at relay contacts and closes a connected solenoid valve in the gas supply line.
A buzzer in the controller gives an acoustic alarm.
Four DC switches (nominal voltage 32VDC/200mA) are incorporated which can be used for
further switching tasks. There are four output relays (230VAC/4A) for connecting further
technical equipment and signalling devices:
- Relay for pre-alarm
- Relay for main alarm
- Relay for acoustic warning devices
- Relay for fault messages
Technical data:
Number of detectors: max. 4 detectors
Detector inputs: 4 x 4-20mA
External reset: yes
Outputs: potential free change over contacts
(230VAC 4A), PhotoMos relay (32VDC 200mA)
Collective alarm for alarm1, alarm2, alarm3 (horn)
Device fault
Alarm device: built in 85dBA signal horn
Display elements: Display for concentration and channel number, LEDs for Alarm 1, 2,
error, ready, measurement
Power supply: 100-240VAV, 47-63Hz, 20W
Emergency power supply: 1 x 24VDC input
Temperature range: -10°C to +40°C
Relative humidity: 10-95% r.h. (non-condensating)
Degree of protection: IP44
Housing: wall-mounting plastic housing
Dimensions: 240x190x90mm
Functional assessment: EN 50194
Electrical safety: EN60335-1
EMC requirements: EN50270 (type1), EN61000-6-3
询价采购Bieler+Lang GmbH Gas Detection System type : GMC Ecoline 8304 12.600742.2 气体检测系统
请用微信扫描下方二维码或手动添加微信号2351992198