adamczewski elektronische messtechnik-measuring converter multifunction converter 测量转换器 多功能转换器 温度转换器 电阻变送器
测量转换器和多功能转换器用于将物理值(如温度或电阻等)转换为模拟标准信号,同时进行限值处理。这些设备通常用于工业自动化和控制系统中,将传感器测得的物理值转化为可用于监控和控制的标准信号。限值处理则允许在特定条件下触发警报或执行其他操作。
多功能转换器
AD-VC 1 GVDInput current | |
---|---|
Measuring range | -24 ... + 24 mA DC |
Input resistance | 20 Ohm |
Basic accuracy | 4 µA |
Transmitter supply | |
Off-load voltage | 24,0 V |
Voltage at 20mA | 18,0 V |
Current limit | ~ 25 mA |
Input voltage | |
Measuring ranges | 0 ... + 12 V DC |
Input resistance | 1 MOhm |
Basic accuracy | 1 mV |
Input voltage mV | |
Measuring ranges | -15 ... +15 mV |
-30 ... +30 mV | |
-60 ... +60 mV | |
-125 ... +125 mV | |
-250 ... +250 mV | |
Input resistance | 1 MOhm |
Basic accuracy | 20 µV |
Thermocouples | |
Comparative place: | |
Internal | Measurement with sensor in the device connecting terminals |
External | Cold junction temperatureselectable by parameters |
To DIN EN 60584: | |
Messbereich Typ J | -200 ... +1200 °C |
Messbereich Typ T | -200 ... +400 °C |
Messbereich Typ K | -200 ... +1360 °C |
Messbereich Typ E | -200 ... +1000 °C |
Messbereich Typ N | -200 ... +1300 °C |
Grundgenauigkeit | 1 K |
To DIN EN 60584: | |
Messbereich Typ S | -40 ... +1760 °C |
Messbereich Typ R | -40 ... +1760 °C |
Messbereich Typ B | +400 ... +1800 °C |
Grundgenauigkeit | 2 K |
After standard ASTM E988: | |
Messbereich Typ C | 0 ... +2320 °C |
Grundgenauigkeit | 2 K |
Resistance input | |
Resistance thermometer inputs DIN EN 60751: Pt100, Pt500 and Pt1000 DIN 43760: Ni100, Ni500 and Ni1000 | |
Messbereich Pt | -200 ... +850 °C |
Messbereich Ni | -60 ... +230 °C |
Kleinste Messspanne | 20 K |
Kurzschlusserkennung | < 20 Ohm |
Grundgenauigkeit | 0,2 K |
Linear resistance | |
Messbereich | 0 ... 4000 Ohm |
Grundgenauigkeit | 0,1 Ohm |
Connection method | 2-, 3- oder 4-wire system |
Sensor supply | 100 µA |
Max line resistance 1) | 50 Ohm/cable |
1) With 2-conductor the line resistance comes as an offset into the measurement. | |
Potentiometer input | |
Connection method | 3-wire system |
Max. Resistance | 50 Ohm ... 100 kOhm |
Sensor supply | <=500µA |
Current outputs | |
Max. output range | -21,5 ... 21,5 mA DC |
Max. burden | 400 Ohm |
Residual ripple | 20 µAss |
Voltage outputs | |
Max. output range | -10,5 ... 10,5 V DC |
Min. burden | 10 kOhm |
Residual ripple | 10 mVss |
Relay outputs A/B | |
Contact type | Potential free changeover |
Max. AC-breaking capacity | 250 V AC, 2 A AC, 50Hz |
Max. DC-breaking capacity | 50 V DC, 2 A DC |
Switching operations | |
Mechanical | 107 |
AC: 230V / 2A, cos(phi)=1 | 6 * 105 |
AC: 230V / 2A, cos(phi)=0,4 | 2 * 105 |
DC: 24V / 1A | 2 * 105 |
Transmission behaviour | |
Linearity error | < 0,2 % of the measuring range |
Rise time | 500 ms (0...90 %, 100...10 %) |
Rise time (temperature input) | < 1s (0...90 %, 100...10 %) |
Temperature influence | +/- 100 ppm/K of the measuring range |
Supply | |
Voltage range AC | 50 ... 253 V AC, 50/60 Hz |
Voltage range DC | 20 ... 253 V DC |
Nominal voltage AC / DC | 230 V AC / 24 V DC |
Power consumption AC / DC | 5,2 VA / 3,2 W |
Power consumption with operating module AC / DC | 5,4 VA / 3,6 W |
Housing | |
Dimensions (WxHxD) | 23x110x134 mm |
With operating module (bxhxt) | 23x110x138 mm |
Type of protection | IP 20 |
Connection method | Detachable terminal clamp |
Terminals, wire cross section | 2,5 mm² flex wire / 4 mm² one wire |
Bolting torque terminals | 0,5 Nm |
Weight | ~ 150 g |
Manner of fastening | 35 mm DIN rail 35mm |
Environmental conditions | |
Ambient temperature | -10 ... 50 °C |
Storage and transport | -10 ... 70 °C (no condensation) |
EMC | |
Product family standard 1) | EN 61326-1 |
Emitted interference | EN 55011, CISPR11 Cl. B, Gr. 1 |
1)During electromagnetic disturbance minor changes in output signal are possible. | |
Electrical safety requirements | |
Product family standard | EN 61010-1 |
Overvoltage category | II |
Pollution degree | 2 |
Galvanic isolation, test voltages | |
Input to output | 2,5 kV (1 min) |
In-/output to auxiliary voltage | 4 kV (1 min) |
温度转换器
VarioCheck VC5B系列Resistance thermometer inputs Pt100, Pt500, Pt1000 to DIN EN 60751 | |
---|---|
Measuring range | -200 ... +850 °C |
Connection method | 2-, 3- oder 4-wire system |
Resolution | 16 Bit |
Accuracy | 0,5 K |
Smallest measuring spans | 20 K |
Max line resistance 1) | 10 Ohm/cable |
Sensor supply | |
Pt100 | 1 mA |
Pt500, Pt1000 | 210 µA |
1) With 2-conductor the line resistance comes as an offset into the measurement. | |
Resistance thermometer inputs Ni100, Ni500, Ni1000 to DIN EN 43760 | |
Measuring range | -60 ... +230 °C |
Connection method | 2-, 3- oder 4-wire system |
Resolution | 16 Bit |
Accuracy | 0,5 K |
Smallest measuring spans | 20 K |
Max line resistance 1) | 10 Ohm/cable |
Sensor supply | |
Ni100 | 1 mA |
Ni500, Ni1000 | 210 µA |
1) With 2-conductor the line resistance comes as an offset into the measurement. | |
Thermocouples | |
Comparative place: | |
Internal | Measurement with LM35 in the device connecting terminals |
External | Cold junction temperatureselectable by parameters |
Resolution | 16 Bit |
Accuracy | 0,2 % of measuring range |
Measuring range type J | -200 ... +1200 °C |
To DIN EN 60584: | |
Measuring range type T | -200 ... +400 °C |
Measuring range type K | -200 ... +1360 °C |
Measuring range type E | -200 ... +1000 °C |
Measuring range type N | -200 ... +1300 °C |
Measuring range type S | -40 ... +1760 °C |
Measuring range type R | -40 ... +1760 °C |
Measuring range type B | +400 ... +1800 °C |
After standard ASTM E988: | |
Measuring range type C | 0 ... +2320 °C |
Smallest measuring spans | 100 K |
Voltage inputs | |
Measuring ranges | -18 ... +18 mV |
-36 ... +36 mV | |
-72 ... +72 mV | |
-144 ... +144 mV | |
Current output 20 mA | |
Output range | 0 ... 20,4 mA |
Resolution | 10 Bit |
Accuracy | 20 µA |
Max. burden | 500 Ohm |
Residual ripple | 20 µAss |
Voltage output 10 V | |
Output range | 0 ... 10,2 V |
Resolution | 10 Bit |
Accuracy | 10 mV |
Min. burden | 5 kOhm |
Residual ripple | 10 mVss |
Werden Stromausgang und Spannungsausgang gleichzeitig benutzt, dürfen die beiden Kreise nicht verbunden werden. | |
Relay outputs A..D | |
Max switching voltage | AC 250 V AC |
Max switching current AC | 2 A AC |
Max switching voltage | DC 50 V DC |
Max switching current DC | 2 A DC |
Display | |
Graphic-LCD | 42x64 Pixel, background RGB lights |
Digital display | 4-digit, can be configured |
Display function | Scaled input signal, input signal, output, limits, scaled dimension as quasi analogue bar, scaling unit |
Transmission behaviour | |
Sampling rate | 1 measure/s |
Linearity error | 0,2 % of full scale |
Temperature influence | +/-100 ppm/K of full scale |
Supply | |
Supply voltage | 50 ... 253 V AC |
20 ... 253 V DC | |
Max power consumption at 24V DC | 2,6 W |
Max power consumption at 230V AC | 5 VA |
Housing | |
Dimension | BxHxT 33x110x128 mm |
Manner of fastening | DIN rail mounting 35mm, EN 50022 |
Type of protection | IP 20 |
Connection method | Detachable terminal clamp, 5 mm grid |
Wire cross section | Max. 2,5 mm2 |
Weight | Ca. 200 g |
Environmental conditions | |
Permissible ambient temperature | -10 ... +60 °C |
Storage and transport | -10 ... 70 °C (no condensation) |
EMC | |
Product family standard 1) | EN 61326-1 |
Emitted interference | EN 55011, CISR11 Cl. B, Gr. 1 |
1) Während der Störeinwirkung sind geringe Signalabweichungen möglich. | |
Electrical safety requirements | |
Product family standard | EN 61010-1 |
Galvanic isolation, test voltages | |
Input to output | 2,5 kV, 1min |
Input/output to auxiliary voltages | 4 kV, 1min |
Outputs together | Nogalvanic isolation |
Input to the programming interface | Nogalvanic isolation |
Resistance thermometer inputs Pt100, Pt500, Pt1000 to DIN EN 60751 | |
---|---|
Measuring range | -200 ... +850 °C |
Connection method | 2-, 3-, 4-wire system |
Resolution | 16 Bit |
Accuracy | 2 K |
Smallest measuring spans | 30 K |
Max line resistance 1) | 10 Ohm / cable |
Sensor supply | |
For 4-wire connection | < 500 µA |
For 2 - and 3-wire connection | < 250 µA |
1) With 2-conductor the line resistance comes as an offset into the measurement. | |
Resistance thermometer inputs Ni100, Ni500, Ni1000 to DIN EN 43760 | |
Measuring range | -60 ... +230 °C |
Connection method | 2-, 3-, 4-wire system |
Resolution | 16 Bit |
Accuracy | 2 K |
Smallest measuring spans | 30 K |
Max line resistance 1) | 10 Ohm / cable |
Sensor supply | |
For 4-wire connection | < 500 µA |
For 2 - and 3-wire connection | < 250 µA |
1) With 2-conductor the line resistance comes as an offset into the measurement. | |
Thermocouples | |
Comparative place: | |
Internal | Measurement at device terminals |
External | Cold junction temperatureselectable by parameters |
Resolution | 16 Bit |
Accuracy | 0,2 % of measuring range |
Measuring range type J | -200 ... +1200 °C |
To DIN EN 60584: | |
Measuring range type T | -200 ... +400 °C |
Measuring range type K | -200 ... +1360 °C |
Measuring range type E | -200 ... +1000 °C |
Measuring range type N | -200 ... +1300 °C |
Measuring range type S | -40 ... +1760 °C |
Measuring range type R | -40 ... +1760 °C |
Measuring range type B | +400 ... +1800 °C |
After standard ASTM E988: | |
Measuring range type C | 0 ... +2320 °C |
Smallest measuring spans | 100 K |
Voltage inputs | |
Measuring range | -18 ... +18 mV |
-36 ... +36 mV | |
-72 ... +72 mV | |
-144 ... +144 mV | |
Resolution | 16 Bit |
Accuracy | 0,2 % of measuring range |
Transmission behaviour | |
Sampling rate | 1 measure / s |
Temperature influence | +/- 100 ppm / K of full scale |
RS485-Bus | |
Software protocol | Modbus-RTU |
Data format | 19200, e, 8, 1 |
Max. bus users | 99 |
Bus termination | 120 ohms both sides at the end |
Max. length of bus | 500 m (no spur lines) |
Cable | Twisted and shielded |
LEDs | |
Green [On] | Supply (blinking on error) |
Yellow [DATA] | RS485 Communication |
Controls | |
Address switch | 01 ... 99 |
Supply | |
Supply voltage | 20 ... 253 V DC / 50 ... 253 V AC |
Max. power consumption | 0,6 W / 1,4 VA |
Housing | |
Dimensions (WxHxD) | 71 x 90 x 58 mm3 |
Manner of fastening | DIN rail mounting 35mm, EN 50022 |
Type of protection | IP 20 |
Connection method | Screw clamp |
Bolting torque terminals | 0,5 Nm |
Wire cross section | Max. 2,5 mm2 |
Weight | Ca. 30 g |
Environmental conditions | |
Permissible ambient temperature | -10 ... +50 °C |
Storage and transport | -10 ... +70 °C (no condensation) |
EMC | |
Product family standard 2) | EN 61326-1 |
Emitted interference | EN 55011, CISPR11 Cl. B, Gr. 1 |
2) During electromagnetic disturbance minor changes in output signal are possible. | |
Electrical safety requirements | |
Product family standard | EN 61010-1 |
Overvoltage category | II |
Pollution degree | 2 |
Galvanic isolation, test voltages | |
Signal / supply unit | 3 kV, 50 Hz (1 min.) |
Signal / RS485 bus | Nogalvanic isolation |
Signal / Signal | Nogalvanic isolation |
电阻变送器
VarioCheck AD-VC 3系列Input current | |
---|---|
Measuring range | -20 ... + 20 mA |
Accuracy | 5 µA |
Input resistance | 60 Ohm |
Voltage input 10V | |
Measuring range | -10 ... + 10 V |
Accuracy | 2,5 mV |
Input resistance | 1 MOhm |
Voltage input 1V | |
Measuring range | -1 ... + 1 V |
Accuracy | 250 µV |
Input resistance | > 1 MOhm |
Potentiometer input | |
Connection method | 3-wire system |
Max. Resistance | 100 Ohm ... 100 kOhm |
Transmitter supply | |
Off-load voltage | 24,5 V |
Voltage at 20mA | 19,5 V |
Current limit | ~ 25 mA |
Output current | |
Max. output range | 0 ... 20,4 mA |
Accuracy | ~ 20 µA |
Max. burden | 500 Ohm |
Residual ripple | 20 µAss |
Output voltage | |
Max. output range | 0 ... 10,2 V (EV: 12,5 V) |
Accuracy | ~ 10 mV |
Min. burden | 5 kOhm |
Residual ripple | 10 mVss |
Resolution | |
Input | 13 bit |
Output | 10 bit |
Relay outputs A...D | |
Contacts R2 / R4 | 2 contacts / 4 contacts |
Max. AC-breaking capacity | 250 V AC, 2 A AC, 50Hz |
Max. DC-breaking capacity | 50 V DC, 2 A DC |
Switching operations | |
Mechanical | 107 |
AC: 230V / 2A, cos(phi)=1 | 6 * 105 |
AC: 230V / 2A, cos(phi)=0,4 | 2 * 105 |
DC: 24V / 1A | 2 * 105 |
DC: 24V / 1A | 2 * 105 |
Display | |
Graphic-LCD | 42x64 Pixel, background RGB lights |
Digital display | 4-digit, can be configured |
Display function | Scaled input signal, input signal, output, limits, scaled dimension as quasi analogue bar, scaling unit |
Transmission behaviour | |
Linearity error | 0,2 % of full scale |
Rise time | 100 ms (output auf 90 %) |
Temperature influence | +/- 100 ppm/K of full scale |
Supply | |
Power supply GF/GVF | 20 ... 253 V DC / 50 ... 253 V AC |
Power supply EV | 20..30 VDC or 50...253 VAC |
Max. power consumption GF | 3,0 W / 5,3 VA |
Max. power consumption GVF | 2,6 W / 5 VA |
Max. power consumption EV | 2,6 W / 5 VA |
Housing GF | |
Dimensions (WxHxD) | 38,5x78x103 mm |
Type of protection | IP 20 |
Connection method | Screw clamp |
Terminals, wire cross section | 2,5 mm² flex wire / 4 mm² one wire |
Bolting torque terminals | 0,5 Nm |
Weight | ~ 215 g |
Manner of fastening | 35 mm DIN rail 35mm |
Housing GVF | |
Dimensions (WxHxD) | 33x110x134 mm |
Type of protection | IP 20 |
Connection method | Detachable terminal clamp |
Terminals, wire cross section | 2,5 mm² flex wire / 4 mm² one wire |
Bolting torque terminals | 0,5 Nm |
Weight | ~ 200 g |
Manner of fastening | 35 mm DIN rail 35mm |
Housing EV | |
Dimensions (WxHxD) | 30,48x128,4x165 |
Type of protection | IP00 |
Connection method | 32-pin male connector |
Weight | ~ 300 g |
Manner of fastening | 19"-Eurocard |
Environmental conditions | |
Ambient temperature | -10 ... 60 °C |
Storage and transport | -10 ... 70 °C (no condensation) |
EMC | |
Product family standard 1) | EN 61326-1 |
Emitted interference | EN 55011, CISPR11 Cl. B, Gr. 1 |
1)During electromagnetic disturbance minor changes in output signal are possible. | |
Electrical safety requirements | |
Product family standard | EN 61010-1 |
Overvoltage category | II |
Pollution degree | 2 |
Galvanic isolation, test voltages | |
Input/output | 2,5 kV (1 min) |
Signal/auxiliary voltage | 3 kV (1 min) |
询价采购adamczewski elektronische messtechnik-measuring converter multifunction converter 测量转换器 多功能转换器 温度转换器 电阻变送器
请用微信扫描下方二维码或手动添加微信号2351992198