adamczewski elektronische messtechnik-measuring converter multifunction converter 测量转换器 多功能转换器 温度转换器 电阻变送器
测量转换器和多功能转换器用于将物理值(如温度或电阻等)转换为模拟标准信号,同时进行限值处理。这些设备通常用于工业自动化和控制系统中,将传感器测得的物理值转化为可用于监控和控制的标准信号。限值处理则允许在特定条件下触发警报或执行其他操作。
多功能转换器
AD-VC 1 GVD
| Input current | |
|---|---|
| Measuring range | -24 ... + 24 mA DC |
| Input resistance | 20 Ohm |
| Basic accuracy | 4 µA |
| Transmitter supply | |
| Off-load voltage | 24,0 V |
| Voltage at 20mA | 18,0 V |
| Current limit | ~ 25 mA |
| Input voltage | |
| Measuring ranges | 0 ... + 12 V DC |
| Input resistance | 1 MOhm |
| Basic accuracy | 1 mV |
| Input voltage mV | |
| Measuring ranges | -15 ... +15 mV |
| -30 ... +30 mV | |
| -60 ... +60 mV | |
| -125 ... +125 mV | |
| -250 ... +250 mV | |
| Input resistance | 1 MOhm |
| Basic accuracy | 20 µV |
| Thermocouples | |
| Comparative place: | |
| Internal | Measurement with sensor in the device connecting terminals |
| External | Cold junction temperatureselectable by parameters |
| To DIN EN 60584: | |
| Messbereich Typ J | -200 ... +1200 °C |
| Messbereich Typ T | -200 ... +400 °C |
| Messbereich Typ K | -200 ... +1360 °C |
| Messbereich Typ E | -200 ... +1000 °C |
| Messbereich Typ N | -200 ... +1300 °C |
| Grundgenauigkeit | 1 K |
| To DIN EN 60584: | |
| Messbereich Typ S | -40 ... +1760 °C |
| Messbereich Typ R | -40 ... +1760 °C |
| Messbereich Typ B | +400 ... +1800 °C |
| Grundgenauigkeit | 2 K |
| After standard ASTM E988: | |
| Messbereich Typ C | 0 ... +2320 °C |
| Grundgenauigkeit | 2 K |
| Resistance input | |
| Resistance thermometer inputs DIN EN 60751: Pt100, Pt500 and Pt1000 DIN 43760: Ni100, Ni500 and Ni1000 | |
| Messbereich Pt | -200 ... +850 °C |
| Messbereich Ni | -60 ... +230 °C |
| Kleinste Messspanne | 20 K |
| Kurzschlusserkennung | < 20 Ohm |
| Grundgenauigkeit | 0,2 K |
| Linear resistance | |
| Messbereich | 0 ... 4000 Ohm |
| Grundgenauigkeit | 0,1 Ohm |
| Connection method | 2-, 3- oder 4-wire system |
| Sensor supply | 100 µA |
| Max line resistance 1) | 50 Ohm/cable |
| 1) With 2-conductor the line resistance comes as an offset into the measurement. | |
| Potentiometer input | |
| Connection method | 3-wire system |
| Max. Resistance | 50 Ohm ... 100 kOhm |
| Sensor supply | <=500µA |
| Current outputs | |
| Max. output range | -21,5 ... 21,5 mA DC |
| Max. burden | 400 Ohm |
| Residual ripple | 20 µAss |
| Voltage outputs | |
| Max. output range | -10,5 ... 10,5 V DC |
| Min. burden | 10 kOhm |
| Residual ripple | 10 mVss |
| Relay outputs A/B | |
| Contact type | Potential free changeover |
| Max. AC-breaking capacity | 250 V AC, 2 A AC, 50Hz |
| Max. DC-breaking capacity | 50 V DC, 2 A DC |
| Switching operations | |
| Mechanical | 107 |
| AC: 230V / 2A, cos(phi)=1 | 6 * 105 |
| AC: 230V / 2A, cos(phi)=0,4 | 2 * 105 |
| DC: 24V / 1A | 2 * 105 |
| Transmission behaviour | |
| Linearity error | < 0,2 % of the measuring range |
| Rise time | 500 ms (0...90 %, 100...10 %) |
| Rise time (temperature input) | < 1s (0...90 %, 100...10 %) |
| Temperature influence | +/- 100 ppm/K of the measuring range |
| Supply | |
| Voltage range AC | 50 ... 253 V AC, 50/60 Hz |
| Voltage range DC | 20 ... 253 V DC |
| Nominal voltage AC / DC | 230 V AC / 24 V DC |
| Power consumption AC / DC | 5,2 VA / 3,2 W |
| Power consumption with operating module AC / DC | 5,4 VA / 3,6 W |
| Housing | |
| Dimensions (WxHxD) | 23x110x134 mm |
| With operating module (bxhxt) | 23x110x138 mm |
| Type of protection | IP 20 |
| Connection method | Detachable terminal clamp |
| Terminals, wire cross section | 2,5 mm² flex wire / 4 mm² one wire |
| Bolting torque terminals | 0,5 Nm |
| Weight | ~ 150 g |
| Manner of fastening | 35 mm DIN rail 35mm |
| Environmental conditions | |
| Ambient temperature | -10 ... 50 °C |
| Storage and transport | -10 ... 70 °C (no condensation) |
| EMC | |
| Product family standard 1) | EN 61326-1 |
| Emitted interference | EN 55011, CISPR11 Cl. B, Gr. 1 |
| 1)During electromagnetic disturbance minor changes in output signal are possible. | |
| Electrical safety requirements | |
| Product family standard | EN 61010-1 |
| Overvoltage category | II |
| Pollution degree | 2 |
| Galvanic isolation, test voltages | |
| Input to output | 2,5 kV (1 min) |
| In-/output to auxiliary voltage | 4 kV (1 min) |
温度转换器
VarioCheck VC5B系列
| Resistance thermometer inputs Pt100, Pt500, Pt1000 to DIN EN 60751 | |
|---|---|
| Measuring range | -200 ... +850 °C |
| Connection method | 2-, 3- oder 4-wire system |
| Resolution | 16 Bit |
| Accuracy | 0,5 K |
| Smallest measuring spans | 20 K |
| Max line resistance 1) | 10 Ohm/cable |
| Sensor supply | |
| Pt100 | 1 mA |
| Pt500, Pt1000 | 210 µA |
| 1) With 2-conductor the line resistance comes as an offset into the measurement. | |
| Resistance thermometer inputs Ni100, Ni500, Ni1000 to DIN EN 43760 | |
| Measuring range | -60 ... +230 °C |
| Connection method | 2-, 3- oder 4-wire system |
| Resolution | 16 Bit |
| Accuracy | 0,5 K |
| Smallest measuring spans | 20 K |
| Max line resistance 1) | 10 Ohm/cable |
| Sensor supply | |
| Ni100 | 1 mA |
| Ni500, Ni1000 | 210 µA |
| 1) With 2-conductor the line resistance comes as an offset into the measurement. | |
| Thermocouples | |
| Comparative place: | |
| Internal | Measurement with LM35 in the device connecting terminals |
| External | Cold junction temperatureselectable by parameters |
| Resolution | 16 Bit |
| Accuracy | 0,2 % of measuring range |
| Measuring range type J | -200 ... +1200 °C |
| To DIN EN 60584: | |
| Measuring range type T | -200 ... +400 °C |
| Measuring range type K | -200 ... +1360 °C |
| Measuring range type E | -200 ... +1000 °C |
| Measuring range type N | -200 ... +1300 °C |
| Measuring range type S | -40 ... +1760 °C |
| Measuring range type R | -40 ... +1760 °C |
| Measuring range type B | +400 ... +1800 °C |
| After standard ASTM E988: | |
| Measuring range type C | 0 ... +2320 °C |
| Smallest measuring spans | 100 K |
| Voltage inputs | |
| Measuring ranges | -18 ... +18 mV |
| -36 ... +36 mV | |
| -72 ... +72 mV | |
| -144 ... +144 mV | |
| Current output 20 mA | |
| Output range | 0 ... 20,4 mA |
| Resolution | 10 Bit |
| Accuracy | 20 µA |
| Max. burden | 500 Ohm |
| Residual ripple | 20 µAss |
| Voltage output 10 V | |
| Output range | 0 ... 10,2 V |
| Resolution | 10 Bit |
| Accuracy | 10 mV |
| Min. burden | 5 kOhm |
| Residual ripple | 10 mVss |
| Werden Stromausgang und Spannungsausgang gleichzeitig benutzt, dürfen die beiden Kreise nicht verbunden werden. | |
| Relay outputs A..D | |
| Max switching voltage | AC 250 V AC |
| Max switching current AC | 2 A AC |
| Max switching voltage | DC 50 V DC |
| Max switching current DC | 2 A DC |
| Display | |
| Graphic-LCD | 42x64 Pixel, background RGB lights |
| Digital display | 4-digit, can be configured |
| Display function | Scaled input signal, input signal, output, limits, scaled dimension as quasi analogue bar, scaling unit |
| Transmission behaviour | |
| Sampling rate | 1 measure/s |
| Linearity error | 0,2 % of full scale |
| Temperature influence | +/-100 ppm/K of full scale |
| Supply | |
| Supply voltage | 50 ... 253 V AC |
| 20 ... 253 V DC | |
| Max power consumption at 24V DC | 2,6 W |
| Max power consumption at 230V AC | 5 VA |
| Housing | |
| Dimension | BxHxT 33x110x128 mm |
| Manner of fastening | DIN rail mounting 35mm, EN 50022 |
| Type of protection | IP 20 |
| Connection method | Detachable terminal clamp, 5 mm grid |
| Wire cross section | Max. 2,5 mm2 |
| Weight | Ca. 200 g |
| Environmental conditions | |
| Permissible ambient temperature | -10 ... +60 °C |
| Storage and transport | -10 ... 70 °C (no condensation) |
| EMC | |
| Product family standard 1) | EN 61326-1 |
| Emitted interference | EN 55011, CISR11 Cl. B, Gr. 1 |
| 1) Während der Störeinwirkung sind geringe Signalabweichungen möglich. | |
| Electrical safety requirements | |
| Product family standard | EN 61010-1 |
| Galvanic isolation, test voltages | |
| Input to output | 2,5 kV, 1min |
| Input/output to auxiliary voltages | 4 kV, 1min |
| Outputs together | Nogalvanic isolation |
| Input to the programming interface | Nogalvanic isolation |

| Resistance thermometer inputs Pt100, Pt500, Pt1000 to DIN EN 60751 | |
|---|---|
| Measuring range | -200 ... +850 °C |
| Connection method | 2-, 3-, 4-wire system |
| Resolution | 16 Bit |
| Accuracy | 2 K |
| Smallest measuring spans | 30 K |
| Max line resistance 1) | 10 Ohm / cable |
| Sensor supply | |
| For 4-wire connection | < 500 µA |
| For 2 - and 3-wire connection | < 250 µA |
| 1) With 2-conductor the line resistance comes as an offset into the measurement. | |
| Resistance thermometer inputs Ni100, Ni500, Ni1000 to DIN EN 43760 | |
| Measuring range | -60 ... +230 °C |
| Connection method | 2-, 3-, 4-wire system |
| Resolution | 16 Bit |
| Accuracy | 2 K |
| Smallest measuring spans | 30 K |
| Max line resistance 1) | 10 Ohm / cable |
| Sensor supply | |
| For 4-wire connection | < 500 µA |
| For 2 - and 3-wire connection | < 250 µA |
| 1) With 2-conductor the line resistance comes as an offset into the measurement. | |
| Thermocouples | |
| Comparative place: | |
| Internal | Measurement at device terminals |
| External | Cold junction temperatureselectable by parameters |
| Resolution | 16 Bit |
| Accuracy | 0,2 % of measuring range |
| Measuring range type J | -200 ... +1200 °C |
| To DIN EN 60584: | |
| Measuring range type T | -200 ... +400 °C |
| Measuring range type K | -200 ... +1360 °C |
| Measuring range type E | -200 ... +1000 °C |
| Measuring range type N | -200 ... +1300 °C |
| Measuring range type S | -40 ... +1760 °C |
| Measuring range type R | -40 ... +1760 °C |
| Measuring range type B | +400 ... +1800 °C |
| After standard ASTM E988: | |
| Measuring range type C | 0 ... +2320 °C |
| Smallest measuring spans | 100 K |
| Voltage inputs | |
| Measuring range | -18 ... +18 mV |
| -36 ... +36 mV | |
| -72 ... +72 mV | |
| -144 ... +144 mV | |
| Resolution | 16 Bit |
| Accuracy | 0,2 % of measuring range |
| Transmission behaviour | |
| Sampling rate | 1 measure / s |
| Temperature influence | +/- 100 ppm / K of full scale |
| RS485-Bus | |
| Software protocol | Modbus-RTU |
| Data format | 19200, e, 8, 1 |
| Max. bus users | 99 |
| Bus termination | 120 ohms both sides at the end |
| Max. length of bus | 500 m (no spur lines) |
| Cable | Twisted and shielded |
| LEDs | |
| Green [On] | Supply (blinking on error) |
| Yellow [DATA] | RS485 Communication |
| Controls | |
| Address switch | 01 ... 99 |
| Supply | |
| Supply voltage | 20 ... 253 V DC / 50 ... 253 V AC |
| Max. power consumption | 0,6 W / 1,4 VA |
| Housing | |
| Dimensions (WxHxD) | 71 x 90 x 58 mm3 |
| Manner of fastening | DIN rail mounting 35mm, EN 50022 |
| Type of protection | IP 20 |
| Connection method | Screw clamp |
| Bolting torque terminals | 0,5 Nm |
| Wire cross section | Max. 2,5 mm2 |
| Weight | Ca. 30 g |
| Environmental conditions | |
| Permissible ambient temperature | -10 ... +50 °C |
| Storage and transport | -10 ... +70 °C (no condensation) |
| EMC | |
| Product family standard 2) | EN 61326-1 |
| Emitted interference | EN 55011, CISPR11 Cl. B, Gr. 1 |
| 2) During electromagnetic disturbance minor changes in output signal are possible. | |
| Electrical safety requirements | |
| Product family standard | EN 61010-1 |
| Overvoltage category | II |
| Pollution degree | 2 |
| Galvanic isolation, test voltages | |
| Signal / supply unit | 3 kV, 50 Hz (1 min.) |
| Signal / RS485 bus | Nogalvanic isolation |
| Signal / Signal | Nogalvanic isolation |
电阻变送器
VarioCheck AD-VC 3系列
| Input current | |
|---|---|
| Measuring range | -20 ... + 20 mA |
| Accuracy | 5 µA |
| Input resistance | 60 Ohm |
| Voltage input 10V | |
| Measuring range | -10 ... + 10 V |
| Accuracy | 2,5 mV |
| Input resistance | 1 MOhm |
| Voltage input 1V | |
| Measuring range | -1 ... + 1 V |
| Accuracy | 250 µV |
| Input resistance | > 1 MOhm |
| Potentiometer input | |
| Connection method | 3-wire system |
| Max. Resistance | 100 Ohm ... 100 kOhm |
| Transmitter supply | |
| Off-load voltage | 24,5 V |
| Voltage at 20mA | 19,5 V |
| Current limit | ~ 25 mA |
| Output current | |
| Max. output range | 0 ... 20,4 mA |
| Accuracy | ~ 20 µA |
| Max. burden | 500 Ohm |
| Residual ripple | 20 µAss |
| Output voltage | |
| Max. output range | 0 ... 10,2 V (EV: 12,5 V) |
| Accuracy | ~ 10 mV |
| Min. burden | 5 kOhm |
| Residual ripple | 10 mVss |
| Resolution | |
| Input | 13 bit |
| Output | 10 bit |
| Relay outputs A...D | |
| Contacts R2 / R4 | 2 contacts / 4 contacts |
| Max. AC-breaking capacity | 250 V AC, 2 A AC, 50Hz |
| Max. DC-breaking capacity | 50 V DC, 2 A DC |
| Switching operations | |
| Mechanical | 107 |
| AC: 230V / 2A, cos(phi)=1 | 6 * 105 |
| AC: 230V / 2A, cos(phi)=0,4 | 2 * 105 |
| DC: 24V / 1A | 2 * 105 |
| DC: 24V / 1A | 2 * 105 |
| Display | |
| Graphic-LCD | 42x64 Pixel, background RGB lights |
| Digital display | 4-digit, can be configured |
| Display function | Scaled input signal, input signal, output, limits, scaled dimension as quasi analogue bar, scaling unit |
| Transmission behaviour | |
| Linearity error | 0,2 % of full scale |
| Rise time | 100 ms (output auf 90 %) |
| Temperature influence | +/- 100 ppm/K of full scale |
| Supply | |
| Power supply GF/GVF | 20 ... 253 V DC / 50 ... 253 V AC |
| Power supply EV | 20..30 VDC or 50...253 VAC |
| Max. power consumption GF | 3,0 W / 5,3 VA |
| Max. power consumption GVF | 2,6 W / 5 VA |
| Max. power consumption EV | 2,6 W / 5 VA |
| Housing GF | |
| Dimensions (WxHxD) | 38,5x78x103 mm |
| Type of protection | IP 20 |
| Connection method | Screw clamp |
| Terminals, wire cross section | 2,5 mm² flex wire / 4 mm² one wire |
| Bolting torque terminals | 0,5 Nm |
| Weight | ~ 215 g |
| Manner of fastening | 35 mm DIN rail 35mm |
| Housing GVF | |
| Dimensions (WxHxD) | 33x110x134 mm |
| Type of protection | IP 20 |
| Connection method | Detachable terminal clamp |
| Terminals, wire cross section | 2,5 mm² flex wire / 4 mm² one wire |
| Bolting torque terminals | 0,5 Nm |
| Weight | ~ 200 g |
| Manner of fastening | 35 mm DIN rail 35mm |
| Housing EV | |
| Dimensions (WxHxD) | 30,48x128,4x165 |
| Type of protection | IP00 |
| Connection method | 32-pin male connector |
| Weight | ~ 300 g |
| Manner of fastening | 19"-Eurocard |
| Environmental conditions | |
| Ambient temperature | -10 ... 60 °C |
| Storage and transport | -10 ... 70 °C (no condensation) |
| EMC | |
| Product family standard 1) | EN 61326-1 |
| Emitted interference | EN 55011, CISPR11 Cl. B, Gr. 1 |
| 1)During electromagnetic disturbance minor changes in output signal are possible. | |
| Electrical safety requirements | |
| Product family standard | EN 61010-1 |
| Overvoltage category | II |
| Pollution degree | 2 |
| Galvanic isolation, test voltages | |
| Input/output | 2,5 kV (1 min) |
| Signal/auxiliary voltage | 3 kV (1 min) |
询价采购adamczewski elektronische messtechnik-measuring converter multifunction converter 测量转换器 多功能转换器 温度转换器 电阻变送器