Analytical Systems Keco, LLC SulfurHound H2S in Gas Process Analyzer SulfurHound Z2 硫化氢分析仪
• Weather-resistant enclosure (UL listed, CSA type, IP66)
• Concentration alarms via Modbus & one relay: High (SPDT Relays, 250 VAC @ 5 Amps)
• Diagnostic Alarms via Modbus & one relay (SPDT relays, 250 VAC @ 5 Amps)
• 4-20mA Analog Output
• MODBUS RS-485 half duplex, TCP/IP Ethernet
• Data Logger using Micro SD card
• Built for Class I Division 2 (Zone 2) Groups B, C, D hazardous location installations
• All wetted parts suitable for H2S service
• Automatic Calibration including remote activation of calibration (SPDT relay, 24VDC @ 5 Amps)
NOTE: Electrochemical Analyzers read mercaptans plus H2S and false high reading will result if mercaptans are present.
• Calibration Range: 0 – 100 ppm by volume H2S in
• Sample Details: Pressure range: approximately 3.6 bar; Temperature range: -25~70 ℃.
• Power (choose one): 24VDC, 120VAC or 220VAC
Human Machine Interface (HMI) 4 Series for analyzers. Includes color touchscreen, processor, core I/O, memory, and loaded program.
NOTE: To replace in existing analyzer, please provide serial number of analyzer installed.
Relay with 6 A power contact, 1 changeover contact, 24 V DC input voltage. Approved according to ATEX/IECEx (Zone 2) and Ex Zone Class I, Div. 2.
Solenoid, 3-way for Atex Cert. Teflon/Kalrez, 1/8 NPT, PTFE elastomers for H2S service, Stainless Steel body, 175PSI, Explosionproof Class I, Div I, 24VDC
Power Supply 24V 204ATEX
Flowmeter with needle valve, SS. Max input pressure 100 psig
Spare sensor for SulfurHound electrochemical H2S sensor for ranges up to 200 ppm. Includes sensor and housing for easy and quick plug and play replacement of sensor. No tools required for replacement.
*Requires analyzer serial number before order can be processed.
询价采购Analytical Systems Keco, LLC SulfurHound H2S in Gas Process Analyzer SulfurHound Z2 硫化氢分析仪
请用微信扫描下方二维码或手动添加微信号2351992198